Emergency Lighting Requirements for UK Businesses: Where It Is Needed and Who Is Responsible

Aaqil Zeyad
Oct 12
11 min read

Updated: 5 days ago

Emergency lighting is required where people would be at risk if normal lighting failed. In England and Wales, fire safety legislation requires suitable emergency illumination of escape routes and exits where necessary, while workplace safety duties can also require lighting to make hazardous activities safe.



The correct provision depends on the premises, its occupants, its operating conditions and the findings of a suitable risk assessment.


For businesses, commercial landlords and facilities managers, this means looking beyond whether an illuminated exit sign has been fitted above the front door.


The important question is whether people could find and use the complete escape route safely during a lighting failure, including stairs, internal corridors and the area beyond the final exit.


This guide explains emergency lighting requirements for UK businesses, with particular attention to London premises.


The legal discussion focuses on England and Wales; Scotland and Northern Ireland have separate fire safety legislation and guidance.


Is Emergency Lighting a Legal Requirement for Businesses?


In England and Wales, the principal fire safety legislation is the Regulatory Reform (Fire Safety) Order 2005.


Article 14 addresses emergency routes and exits, including adequate emergency illumination where necessary if normal lighting fails.


Article 17 requires relevant fire safety equipment to be kept in effective working condition through suitable maintenance.


That does not mean every business needs an identical installation.


The assessment concerns what would happen in the actual premises, considering its layout, use and occupants.


A small ground-floor shop with an obvious exit presents a different escape problem from a basement restaurant or a multi-storey office.


Small premises are not automatically exempt. 


Government guidance allows for limited situations in which adequate, dependable “borrowed light” could make dedicated emergency escape lighting unnecessary.


Borrowed light comes from another source, such as external lighting, and must be expected to remain available whenever it is needed.


For example, daylight through a shop window does not establish that a rear stockroom or staircase will be safe during winter evenings.


Street lighting also needs scrutiny: it may be switched off, obstructed or affected by the same power failure.


A decision to rely on borrowed light should therefore be justified in the assessment, not based on how bright the premises looked during one daytime visit.


The FIA specifically warns that assumptions about external lighting need reassessment where street-lighting arrangements change.


Who Is Responsible: The Employer, Landlord or Facilities Manager?


In a workplace under an employer’s control, the employer normally holds the Responsible Person duties under the Fire Safety Order.


Owners, landlords, occupiers and others can also have duties according to their control over the premises.


Where responsibilities overlap, the relevant parties must cooperate and coordinate their fire safety arrangements.


A useful illustration is a shared London office building.


The landlord might arrange testing of emergency lights in communal stairs, while individual tenants manage fittings inside their own offices.


The practical risk is a gap between those arrangements: everyone assumes that somebody else is checking the lobby, basement passage or external escape stair.


A sensible management record should identify who arranges tests, who receives fault reports, who authorises repairs and who keeps the documentation.


It should also establish how tenants are notified when a shared escape route is affected.


These arrangements should support the building’s coordinated emergency plan, which London Fire Brigade says should address escape routes, lighting where needed, responsibilities and the needs of vulnerable occupants.


Appointing a contractor can help fulfil these responsibilities, but it is not a reason to stop reviewing the condition of the system.


The business still needs a process for responding to defects and ensuring that agreed work is completed.


Where Should Emergency Lighting Be Installed?


The layout should follow the escape routes, relevant hazards and safety equipment identified for the premises.


Government guidance identifies locations such as exit doors, corridor junctions, stairs, changes in floor level, external escape routes and firefighting equipment.


It also makes clear that a separate fitting is not necessarily required beside every individual feature, provided the overall illumination is adequate.


For most commercial assessments, the main functions to consider are:

  • Escape-route lighting: Helps people follow corridors, stairs and other routes towards safety, recognising changes of direction and level.

  • Open-area lighting: Helps occupants orient themselves and reach an escape route from a larger open space.

  • High-risk task lighting: Provides suitable illumination where a sudden loss of light could make an activity dangerous or prevent safe shutdown.


These functions should be considered together rather than treating emergency lighting as a row of identical fittings.


The equipment selected depends on the purpose of each area, including escape routes, open spaces, exit signs and high-risk tasks.


The assessment should also consider windowless rooms, relevant toilet facilities, refuges and assistance points, first-aid equipment, fire alarm call points and equipment that must remain visible during an emergency.


High-risk areas need particular attention where machinery or another hazardous process cannot be made safe without adequate light.


The route does not necessarily end at the external door. 


Steps, ramps, passageways or other hazards immediately outside may need illumination so that people can continue towards a place of safety.


This is especially relevant where a business exits into a dark rear yard rather than directly onto an adequately lit pavement.


Exit signs and escape lighting also perform different jobs.


A sign identifies the direction or location of an exit; lighting helps people negotiate the route.


Signs must remain visible and understandable under the relevant conditions, but their presence alone does not demonstrate that the surrounding floor, stairs or obstacles are adequately illuminated.


🟥 An illuminated exit sign is not proof that the whole escape route is adequately lit. Review what people would actually need to see between their starting point and a place of safety.

Which Emergency Lighting Standards Apply?


The principal UK code of practice is now BS 5266-1:2025, which replaced the 2016 edition.


BSI describes it as guidance on the design, installation and wiring of emergency lighting systems, with an expanded scope that includes local-area and standby lighting alongside emergency escape lighting.


Two related standards are particularly important.


BS EN 1838:2024 addresses the lighting performance required, while BS EN 50172:2024 addresses emergency escape lighting systems, including installation, verification, monitoring, maintenance and documentation.


Their roles overlap in supporting a complete design, rather than providing three interchangeable ways to specify the same thing.


These are technical standards, not separate Acts of Parliament.


The legal duty is to provide and maintain appropriate safety measures; standards supply recognised technical criteria that help designers, installers and those managing premises demonstrate how those duties have been addressed.


Current editions matter. BSI’s summary of BS EN 1838:2024 identifies changes to escape-route illumination, including moving beyond the previous centre-line approach.


A design based solely on an old internet diagram or an assumed distance between fittings may therefore miss relevant requirements.


For an existing installation, the useful starting point is a competent review of its condition, performance and suitability for current use.


Avoid assuming either that an older system must be replaced completely or that it remains adequate simply because the lights still switch on.


AZ’s existing emergency lighting regulations guide provides related background, while a building-specific assessment is needed to establish the appropriate work.


Maintained Lighting, Battery Systems and Required Duration


Maintained emergency lighting operates during normal conditions and continues on its emergency supply when needed.


Non-maintained lighting normally illuminates only when the relevant normal lighting supply fails.


These terms describe operating mode; they do not mean that one type requires maintenance and the other does not.


The power arrangement is a separate choice.


A self-contained fitting has its own emergency battery, while a central-battery system supplies multiple fittings from a shared source.


Neither arrangement is automatically correct for every building: the design should account for the layout, maintenance arrangements and intended operation.


Three-hour emergency lighting is common in UK premises, but it is not a universal statutory duration for every business. 


Industry guidance distinguishes situations where rapid evacuation without early reoccupation may permit a shorter duration from premises where longer protection is needed, including sleeping accommodation or circumstances where evacuation cannot be immediate.


The required duration should be selected for the premises, not simply chosen from the cheapest available battery option.


Duration and brightness are both important.


A fitting that remains on for the specified period may still be unsuitable if it cannot illuminate the required area adequately.


Conversely, a bright light that fails before its rated duration has not demonstrated the required endurance.


Emergency escape lighting should not automatically be treated as permission to continue normal business during a power cut.


Lighting that allows people to leave safely is different from lighting suitable for continued occupation or normal work.


BSI’s revised code recognises these additional functions, but they require appropriate assessment and design.


How Often Should Emergency Lighting Be Tested?


The legal requirement is to maintain effective fire safety measures.


The detailed testing regime is established through relevant standards, system instructions and competent advice, rather than a single clause in the Fire Safety Order prescribing the same test for every installation.


For a typical battery-backed system, recognised guidance describes monthly functional testing and an annual test for the full rated duration.


Daily visual checks of central controls may also apply where the installation has central equipment.


These are different checks with different purposes.


The monthly test establishes that the emergency lights operate when tested.


It needs to last long enough for the relevant fittings to be checked; switching a test facility briefly without inspecting the lights is not a meaningful assessment.


The annual duration test establishes whether the system can provide its emergency output for the period for which it is rated.


Full-duration testing must be planned carefully because it uses battery capacity.


Government guidance warns that batteries may typically need around 24 hours to recharge, and the premises should not be reoccupied without a fully functioning system unless suitable alternative arrangements have been made.


The actual recovery time and precautions should be confirmed for the installed equipment.


Routine tests may be carried out by appropriately instructed staff where they understand the procedure and the system permits it.


The government’s small-premises guidance calls for annual emergency-lighting inspection and testing by a competent contractor.


Staff should not improvise electrical isolation or open fittings without the necessary competence.


Automatic self-testing equipment can reduce manual test work, but it does not remove the need to review results, address faults and check the physical installation.


BS EN 50172:2024 specifically includes provisions for automatic test systems and continued monitoring.


What Should Happen When an Emergency Light Fails?


A failed fitting, inadequate duration or fault indication should trigger action—not simply another entry in a logbook.


The immediate question is what the failure means for safety.


A defect affecting the only adequately lit stair route could have different consequences from one where verified alternative coverage remains available.


The FIA advises recording faults, notifying the maintenance provider and assessing the circumstances to determine the necessary response.


Where protection has been reduced, suitable temporary precautions may be necessary while competent repairs are arranged.


In some circumstances, affected activities or areas may need to be restricted.


There is no sensible universal promise that every failure can wait until the next scheduled service, and BAFE’s guidance emphasises logging failures and introducing alternative safety procedures until repairs are completed.


The repair also needs to be appropriate to the installed equipment.


The issue may require replacement of a battery, component or complete fitting, followed by suitable verification.


Merely clearing a fault indication does not establish that the system has regained its required performance.


AZ Electrical provides emergency lighting testing and servicing for businesses that need testing, fault investigation and associated repairs.


What Records Should a Business Keep?


The fire risk assessment and fire safety arrangements must be recorded under the current requirements applying to Responsible Persons.


Since October 2023, the recording duty has not been limited to businesses with five or more employees.


A small workforce is therefore not a reason to rely entirely on an undocumented assessment.


For the lighting system itself, keep the available design and installation information, commissioning or verification records, operating instructions and maintenance documentation.


The current BS EN 50172 standard includes strengthened handover and documentation provisions, reflecting the importance of knowing what has been installed and how it should be managed.


A practical logbook should identify the fitting or area tested, the date, the result, any defect and the corrective action.


Numbering fittings and matching them to a simple plan can make this much easier.


“Emergency light failed” is less useful than a record that identifies the particular landing, exit or room affected.


Keep evidence that repairs were completed, not just evidence that they were recommended.


BAFE’s guidance stresses keeping test and repair records up to date and retaining the relevant documents for reference.


These records can also be relevant during enforcement inspections.


London Fire Brigade asks businesses to have fire safety records available and can respond to deficiencies with advice, notices or restrictions according to the risk.


An annual test document is useful evidence, but it does not remove the need to deal with subsequent faults or changes.


Refurbishments, Changed Opening Hours and Shared London Premises


Emergency lighting should be reviewed alongside changes to the premises.


The fire risk assessment must be regularly reviewed and updated, considering escape routes, emergency arrangements and the needs of people at risk.


A refurbishment can change those conditions even when none of the existing fittings has failed.


Consider an illustrative office refit.


Adding partitions could turn a previously open area into enclosed rooms, alter the route to an exit or obstruct light reaching a corridor.


The relevant question is not just whether the old lights still operate, but whether they still illuminate the new layout adequately.


Opening hours can create another change.


A shop previously used only in daylight might begin evening trading, while cleaners or stockroom staff could remain after customers leave.


Any assessment relying on external or natural light needs to reflect those actual occupancy periods rather than only the advertised customer hours.


Shared buildings need coordinated review too.


If one tenant alters a lobby or access route used by another occupier, the effect can extend beyond that tenant’s own floor area.


Employers, landlords and managing agents should make sure the emergency plan remains consistent with the building’s current arrangements.


London Fire Brigade’s workplace guidance treats lighting, escape routes, signs and assistance arrangements as parts of the same emergency plan.


Reviewing them together is more useful than commissioning separate pieces of work without checking how they fit together.


Planning Emergency Lighting for Your London Business


A useful review starts with the route people will actually take, the hazards they may encounter and the evidence available about the existing system.


Before commissioning work, gather the current fire risk assessment, any lighting drawings, recent test reports and details of unresolved faults.


Use the following questions to organise the brief:

  • Need: Which occupied areas would become unsafe if normal lighting failed?

  • Coverage: Can people identify and use the entire escape route, including stairs and external sections?

  • Responsibility: Who manages shared areas, routine checks and repair authorisation?

  • Performance: What lighting output, operating mode and duration does the design require?

  • Testing: Are functional and duration tests being completed, recorded and followed up?

  • Change: Have alterations, occupancy or opening hours made previous assumptions unreliable?


This is a planning checklist rather than a substitute for a fire risk assessment or technical lighting design.


Its purpose is to make sure the right questions reach the appropriate professionals before equipment is selected.


AZ Electrical provides emergency lighting installation in London, alongside testing and servicing for existing systems.


Its services cover commercial premises in London and surrounding areas.


If your premises have missing coverage, an overdue test, failed fittings or a changed layout, contact AZ Electrical to discuss the installation, testing or remedial work required.


Provide the available assessment and test records so the proposed work can address the actual building, rather than an assumed number of lights.


Sources and Further Reading














About the Author


Aaqil Zeyad is the owner of AZ Electrical Engineering Services Ltd, a London-based residential and commercial electrical contractor.


AZ Electrical provides emergency lighting installation, testing and servicing alongside electrical and fire alarm services for businesses and property owners.


Find out more about emergency lighting installation, arrange testing and servicing, or contact AZ Electrical to discuss your premises.

 
 
 

Comments


Commenting on this post isn't available anymore. Contact the site owner for more info.
bottom of page